Product type | Uninterrupted power supply; Online |
Model | PM 10000E Online LCD |
Capacity | 10000VA / 7000W |
Product type | Uninterrupted power supply; Online |
Model | PM 10000E Online LCD |
Capacity | 10000VA / 7000W |
Protection | Full protection against discharge, overcharge and overload |
Input | Phase: Single phase with ground |
Frequency range: 46Hz – 54Hz / 54 – 64Hz | |
Power factor: 0.7 | |
Voltage range: Line low transfer 176VAC/140VAC/120VAC/110VAC (±5V) |
|
Voltage range Line low comeback 186VAC/150VAC/130VAC/120VAC (±5V) |
|
Voltage range Line high transfer 276VAC (±5V) |
|
Voltage range Line high comeback 266VAC (±5V) |
|
Output | Phase: Single |
Voltage: 208VAC/220VAC/230VAC/240VAC | |
Voltage regulation: ± 2 % | |
Frequency (sychronized range): 46Hz – 56Hz / 54 – 64Hz | |
Frequency (Batt. mode): 1 Hz/s | |
Current crest ratio: 3:1 | |
Harmonic distortion: ≦4% THD (Linear Load) |
|
Harmonic distortion: ≦7% THD (Non-Linear Load) |
|
Output waveform (Batt. mode): Pure sine wave | |
Efficiency | To AC mode: 88% |
To Battery mode: 88% | |
Battery | Battery type: 12V / 9AH |
Numbers of batteries: 16 | |
Backup time (65% Load): >5minutes | |
Recharge time: 5h charge to 90% | |
Charging current (Max.): 1.0A | |
Charging voltage: (218.4±1%)VDC | |
Transfer time | AC to DC: Zero |
Inverter to bypass: 5ms(Typical) | |
Indicator | Status(LED): Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault |
Status(LCD): Load Level / Battery Level / Input / Output / Operating Mode Information |
|
Audible alarm | Battery mode: Sounding every 4 seconds |
Low battery: Sounding every second | |
Overload: Sounding twice every second | |
Fault: Continously sourding | |
Physical | Dimension, D*W*H (mm): 509 * 200 * 735 |
Net weight (kgs): 70 | |
Environment | Operating environment: 0~40℃, 20~90% relative humidity (non-condensing) |
Noise level: < 55dB @ 1 Meter | |
Interface | Smart RS-232: Support WinPower software |
SNMP (option): Power management from SNMP manager and web brower | |
Accessories | IEC output cable x1 (for PM 1000E-3000E Online LCD only),RS-232 cable x1,application CD,user guide |