Product type | Uninterrupted power supply; Online |
Capacity | 3000 VA / 2400 W |
Product type | Uninterrupted power supply; Online |
Capacity | 3000 VA / 2400 W |
Product type | Uninterrupted power supply; Online |
Capacity | 3000 VA / 2400 W |
Input | Voltage Range Low line transfer: “160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % (based on load percentage 100% – 80% / 80% – 70% / 70% – 60% / 60% -0) “ |
Voltage Range Low line/Comeback: 175 VAC ± 5 % or 85 VAC ± 5 % |
|
Voltage Range High line transfer: 300 VAC ± 5 % or 150 VAC ± 5 % |
|
Voltage Range Low line/Comeback: 290 VAC ± 5 VAC or 143 VAC ± 3 VAC |
|
Frequency range: 40 Hz ~ 70 Hz |
|
Phase: Single phase with ground |
|
Power factor: ≧ 0.99 @ 220-230 VAC (input voltage) |
|
Output | AC voltage regulation (Batt. mode): ±1 % |
Frequency range (Synchronized Range): 47 ~ 53 Hz or 57 Hz ~ 63 Hz | |
Frequency range (Batt. mode): 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | |
Current crest ratio: 3:1 | |
Harmonic distortion: ≦ 4 % THD (Linear Load) ≦ 7 % THD(Non-linear Load) |
|
Transfer time AC to DC: Zero | |
Transfer time Inverter to Bypass: 4 ms (Typical) | |
Waveform (Batt. mode): Pure Sine Wave | |
Efficiency | To AC mode: 88% |
To battery mode: 83% | |
Battetry | Battery voltage: 12 V / 9 Ah x 6 |
Typical recharge time: 4 hours recover to 90% capacity | |
Charging current (max.): 1.0 A | |
Charging voltage: 82.1 VDC ± 1% | |
Long-run model Battery voltage: Depending on the capacity of external batteries | |
Long-run model Typical recharge time: / | |
Long-run model Charging current (max.): 8.0 A | |
Long-run model Charging voltage: 82.1 VDC ± 1% | |
Indicators | LCD Panel: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
Alarm | Battery mode: Sounding every 4 seconds |
Low battery: Sounding every second |
|
Overload: Sounding twice every second |
|
Fault: Continuously sounding |
|
Physical | Standard model Dimension, DXWXH (mm): 580 X 438 X 133 [3U] |
Standard model Net weight (kg): 31 | |
Long-run model Dimension, DXWXH (mm): 580 X 438 X 133 [3U] |
|
Long-run model Net weight (kg): 17 |
|
Operating environment | Humidity: 20-90 % RH @ 0- 40°C (non-condensing) |
Noise level: Less than 45dB @ 1 Meter | |
Management | Smart RS-232/USB: Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, and MAC |
Optional SNMP: Power management from SNMP manager and web browser | |
Accessories | IEC outlet cable x 2, USB cable, User guide, Software CD, optional: SNMP card |
Weight | 32 kg |
---|
20x15 product image 300dpi PowerMust 3024 Online LCD RM.jpg | 0.9mb | 14-07-2017 | |
20x15 product image 300dpi PowerMust 3024 Online LCD RM rear.jpg | 1mb | 14-07-2017 |
Product info PM1008 2016 3024 (L) Online LCD RM -En.pdf | 0.9mb | 14-07-2017 |
PowerMust1008-3024 Online LCD RM -En.pdf | 2.7mb | 14-07-2017 |