Mustek PowerMust 10000 RM Sinewave LCD Online IEC

Out of stock

Mustek PowerMust 10000 RM Sinewave LCD Online IEC

Features

  • Pure Sine Wave
  • True double-conversion online UPS
  • Wide input voltage range (110-300VAC)
  • Output Power factor 1
  • Emergency power off (EPO) function
  • Active input power factor correction 0,99
  • Generator compatible
  • 50Hz/60Hz frequency converter mode
  • SNMP/USB/RS-232 communications
  • Optional N+X parallel redundancy
  • Adjustable battery numbers

 

SKU: 10000-LCD-ON-R20 Categories: , ,
Specification
MODEL PowerMust 6000 LCD, RM PowerMust 10000 LCD, RM
INPUT
Capacity 6000VA/6000W 10000VA/10000W
Voltage Range 110-300VAC@(0-60%) load;140-300VAC @(60-80%) load; 176-300VAC@(80-100%) load
THDI < 4% @ 100, < 6% @ 50% load
Frequency Range 46-54 Hz@ 50Hz / 56-64 Hz@ 60Hz
Phase Single phase with ground
Power Factor ≥ 0.99 @ full load
OUTPUT
Output voltage 208/220/230/240 VAC
AC Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46-54 Hz@ 50Hz / 56-64 Hz@ 60Hz
Frequency range ( Batt. Mode) 50 or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≤1,5% THD (Linear Load); ≤7% THD (non-Linear Load)
Waveform (Batt. Mode) Pure Sinewave
BATTERY
Battery Type 12 V / 7 AH x 16 12 V / 9 AH x 16
Recharge Time 9 hours recover to 90% capacity
Charging Current 1 A (max.)
BACK-UP TIME
Back up time > 4 min. > 2,5 min.
AUDIBLE ALARM
Battery Mode Sounding every 4 seconds
Battery Low Sounding every second
Fault Continuesly sounding
Overload Sounding twice every second
TRANSFER TIME
BAT <–> LINE 0 ms 0 ms
INV <–> BYPASS 0 ms 0 ms
INV –> ECO 0 ms 0 ms
ECO–> INV < 10 ms <10 ms
PHYSICAL
Dimension, D X W X H (mm) 600 x 438 x 88 (2U) 600 x 438 x 88 (2U)
Net Weight (kgs), with batteries 48 48
ENVIRONMENT
Operation Environment 0-40˚
Relative Humidity 20-95% (non-condensing)
Noise Level < 55 dB @1 Meter < 58dB @ 1 Meter
INTERFACE
EPO Emergency Power Off
Intelligent slot External Type of SNMP / RS485 / AS 400 / USB card
USB port Yes
ACCESSORIES
Accessories User manual, EPO connector x1, Input power cord schuko, USB cable x 1,pedestal for tower installation x2, Fitting Ear for UPS x2, Fitting Ear for PDU x1( 10900 x2), Software CD
MANAGEMENT
Smart RS 232 or USB Port Supports Windows® 2000/2002/XP/Vista/2008/7/8/10, Linux and MAC
Optional SNMP Power Management from SNMP manager and Web browser

Additional information

Weight 5.2 kg
PM 6000-10000 LCD RM Online IEC back.jpg0.5mb20-09-2017
PM 6000-10000 LCD RM Online IEC front.jpg1.6mb20-09-2017
6000-10000 LCD RM Online rev 1.pdf0.7mb25-05-2018
PowerMust 6000_10000 RM LCD Online IEC.pdf3.3mb04-06-2018
Skip to toolbar